CYC25 Pressure Transmitter Overview

CYC25 is a pressure transmitter widely used in industrial process control, supporting multiple pressure types and output signals. Its core advantages lie in high precision, strong stability, and easy installation, making it suitable for scenarios such as water treatment, petrochemicals, and power.

This manual provides a Chinese version download to help users quickly complete selection, installation, and commissioning. The following content is compiled based on official materials for reference by engineering technicians and procurement personnel.

CYC25 Chinese Manual PDF Icon Download CYC25 Chinese Manual.pdf

Main Technical Parameters

The table below lists the typical specifications of the CYC25. Specific values may vary by model; please refer to the actual product label.

Parameter ItemSpecification Description
Measurement Range0~0.1MPa to 0~100MPa (optional)
Output Signal4~20mA, 0~10V, RS485 (optional)
Power Supply12~36VDC (typically 24VDC)
Accuracy Class±0.5%FS, ±0.25%FS (optional)
Process ConnectionG1/2, M20×1.5, NPT1/2, etc.
Protection RatingIP65 (standard)
Medium Temperature-20~85℃

Installation and Wiring Guide

Installation Steps

  1. Confirm that the pipeline pressure is within the transmitter's range, and close the valve to release pressure.
  2. Weld or thread the mounting base onto the pipeline, ensuring a good seal.
  3. Screw the CYC25 into the base and tighten with a wrench, avoiding excessive force that may damage the threads.
  4. Check the electrical interface and connect the power and signal lines according to the wiring diagram.
  5. Slowly open the valve and observe whether the output is normal. Perform zero calibration if necessary.

Wiring Key Points

  • Two-wire system: Connect the positive power supply to the transmitter's "+", and the signal line to "-" with a load resistor in series.
  • Three-wire system: Power positive, signal positive, and common ground correspond to the terminals respectively.
  • RS485: Connect A to A, B to B, and ground the shield at one end.

Calibration and Maintenance

Regular calibration ensures measurement accuracy. It is recommended to calibrate once every 12 months, or shorten the cycle according to working conditions.

  • Zero calibration: Under no pressure, adjust the zero potentiometer so that the output is 4mA (or 0V).
  • Full-scale calibration: Apply full-scale pressure and adjust the span potentiometer so that the output is 20mA (or 10V).
  • Cleaning: Wipe the housing with a soft cloth; avoid using corrosive solvents.
  • Inspection: Regularly check whether the sealing rings and wiring terminals are loose or corroded.

Selection and Ordering Information

When selecting, the following parameters must be specified to ensure that the CYC25 meets on-site requirements.

Selection ItemOptional Specifications
Pressure TypeGauge pressure, absolute pressure, sealed pressure
RangeSpecific pressure range
Output4~20mA, 0~10V, RS485
Accuracy±0.5%FS, ±0.25%FS
Process ConnectionG1/2, M20×1.5, NPT1/2
Electrical ConnectionHirschmann, aviation plug, direct cable

For complete technical information, please download the CYC25 Chinese Manual, which includes detailed dimension drawings, wiring diagrams, and troubleshooting.

CYC25 Chinese Manual Download Link Download CYC25 Chinese Manual.pdf