CPM223 PH Transmitter Spare Parts Overview

The CPM223 PH transmitter is widely used in industrial process control, and its spare parts selection directly affects equipment maintenance efficiency and operational stability. This article summarizes the commonly used spare part order numbers, specifications, and applicable scenarios for the CPM223 series transmitters, facilitating quick reference for engineering technicians and procurement personnel.

Spare parts categories include: relay output modules, power modules, housing accessories, mainboards, terminal blocks, communication modules, and software upgrade packages, etc. The following is a detailed list by category.

Relay Output Modules

Relay modules are used to expand the transmitter's digital output capability, supporting various contact configurations and current inputs. When purchasing, pay attention to the number of contacts and whether they include 4-20mA current input.

Order NumberSpecification DescriptionRemarks
51500320Relay output module, 2 floating changeover contactsLIQUISYS-M basic version upgrade
51511446Relay module, 2 floating changeover contactsLIQUISYS-M basic version upgrade
51500321Relay output circuit board, 4 floating changeover contactsLIQUISYS-M basic version upgrade
71129943Relay module, 4 dry changeover contacts, with protective coatingElectronics with protective coating
51511447Relay module
51504304Relay output module, 2 contacts + 4-20mA current inputLIQUISYS-M basic version upgrade
51504305Relay output module, 4 contacts + 4-20mA current inputLIQUISYS-M basic version upgrade

Note: If cleaning function (Chemoclean) is required, the 4-relay board (order number 51500321) must be ordered separately.

Power Modules

The CPM2X3 transmitter supports AC and DC power supply. Spare parts include power supply kits and versions with protective coating.

Order NumberSpecification Description
51500317CXM2X3 AC power supply kit
71129939CXM2X3 AC power supply 100/115/230 V AC, with protective coating
51500318CXM2X3 DC power supply kit

Housing and Mechanical Accessories

Housing accessories are used for mechanical assembly and protection of the transmitter, including side panels, bottom covers, terminal blocks, etc.

Order NumberSpecification Description
51501075CXM223 housing assembly kit
51501076CXM223 mechanical housing parts kit
51502124CXM223 side panel kit
51502513CXM223 Profibus DP bottom cover kit
51501086CXM223 grounding terminal block kit
51501078CXM223 terminal block kit
71071440CXM223 front panel + 6 key riser kit

Mainboards and Communication Modules

The mainboard is the core of the transmitter. Different models support communication protocols such as HART, Profibus PA/DP, etc. When purchasing, confirm the communication type and hardware version.

Order NumberSpecification DescriptionRemarks
51507096MKP2 accessory pack, pH input module MEK
51518244Transmitter module for pH glass electrodes and ORP sensors
51514966Universal digital transmission spare part
71129957Digital transmitter housing, CPM2x3 MKD1 transmitter module for Memosens communication, with protective coatingElectronics with protective coating
51501081CPM2X3 mainboard I1 kit
51501083CPM2X3 mainboard I1 HART kit
71129949CPM2X3 mainboard, 1 current output, with HART, with protective coatingElectronics with protective coating
51501082CPM2X3 mainboard I2 kit
51501084CPM2X3 mainboard I2 HART kit
51501085CPM2X3 mainboard Profibus PA kit
51502503CPM2X3 main module Profibus DP kit
71134724CPM2X3 mainboard, Profibus DP, module name LSCP-DP, hardware 2.10 and above
71134732Relay module Profibus DP, 2 relays + 1 current input DP connection, hardware 2.10 and above

Terminal Blocks and Connectors

Terminal blocks are used for signal and power connections. Different models correspond to different communication protocols.

Order NumberSpecification Description
51501205CUM223 terminal block kit
51501077CPM223 terminal block kit
51502125CPM223 terminal block Profibus PA kit
51502494CPM223 terminal block Profibus DP kit
51501070CPM223 coaxial cable plug-in slot with display board kit
50074961BNC plug, for connecting pH measuring cable (panel-mounted transmitter)
50047795Housing mounting bracket

Software Upgrade Packages

Software upgrade packages can extend transmitter functions. The instrument serial number must be provided. Some upgrade packages need to be used with hardware modules.

  • 51500385: Extended software upgrade package, upgrades LIQUISYS-M basic version to S version (plus package), supports pH, conductivity, temperature, chlorine, oxygen and other parameters. Instrument serial number required.
  • 51500963: Cleaning function upgrade package, adds Chemoclean cleaning function. Instrument serial number required. If the 4-relay board is not installed, order 51500321 separately.

Selection and Ordering Notes

  1. Confirm the transmitter model and hardware version, especially the Profibus DP module requires hardware 2.10 and above.
  2. Distinguish between basic and upgraded functions, and select relay modules or software upgrade packages as needed.
  3. Electronics with protective coating are suitable for harsh environments, such as 71129943, 71129939, etc.
  4. Be sure to provide the instrument serial number when ordering software upgrade packages.
  5. Terminal blocks must match the communication protocol (HART, Profibus PA/DP).

Correct selection ensures long-term stable operation of the CPM223 PH transmitter and reduces maintenance costs. If in doubt, consult the manufacturer or authorized distributor.