MLTTS01 Spare Parts List Overview

The MLTTS01 spare parts list is an important maintenance reference for industrial temperature measurement systems, including key components such as thermocouple inserts and temperature transmitters. Correct selection ensures measurement accuracy and system reliability. This guide is based on the original spare parts list and provides clear, structured information for engineering technicians and procurement.

MLTTS01 Spare Parts List

Spare Parts List and Specifications

General Spare Parts

Order NumberSpecificationPackaging Unit
71367427Spare parts kit ring D21/di 10xgreen10 pieces
71389488Extension cable TC IEC 2x type K, L=180mm3 pieces

Thermocouple Insert TPC100

The TPC100 is a replaceable insert using MgO insulation, suitable for a variety of environments. When selecting, attention must be paid to parameters such as certification, insertion length, and diameter.

  • Certification Options: A-Non-hazardous area; B-ATEX II1D Ex ia IIIC, II1G Ex ia IIC T6
  • Insertion Length IL: XX mm or YY mm (TSP number must be specified)
  • Insertion Diameter: 6mm
  • Head Transmitter: C-Terminal block; F-Flying lead
  • Thermocouple Type: B-2x type K, cl.1; Alloy600, max. 1100°C
  • Standard and Hot Junction: 1-EN 60584 standard; ungrounded

iTHERM TS111 Insert

The TS111 is a replaceable insert conforming to the DIN43735 metric version, suitable for high-vibration environments.

  • Certification: AA-Non-hazardous area; BA-ATEX II1G Ex ia IIC T6
  • Sensor Version: 1-RTD
  • Sensor Type: 1B-PT100 TF, StrongSens vibration-resistant up to 60g; -50...+500°C
  • Insertion Diameter: C-6mm
  • Sensor Standard: 1-IEC 60751 (a=0.03851 Ohm/K)
  • Accuracy Class: 1-Class A (IEC 60751)
  • Number of Sensors: 212-1x StrongSens, class A, 6mm
  • Sheath Material and Design: AC2-316L; 4-wire MI cable (6mm)
  • Insertion Length: X1-..... mm
  • Tests and Certificates: JA-3.1 material certificate; JC-3.1 material certificate summary; K4-penetrant test; KE-pressure test
  • Marking: Z2-device tag (TAG)

Modular Temperature Transmitter TMT182

The TMT182 is a HART protocol temperature transmitter supporting RTD, TC, Ohm, and mV inputs, 2-wire 4-20mA, SIL2, electrically isolated.

  • Certification: A-Non-hazardous area; B-ATEX II1G Ex ia IIC T4/T5/T6
  • Configuration Connection: 1-Thermocouple TC, SIL2; 4-RTD 4-wire, SIL2
  • Configuration Sensor Type: 1-Pt100, -200...850°C; K-Type K, -200...1370°C
  • Configuration: B-Measuring range see additional specifications
  • Additional Options: A-Standard DIN mounting kit

Modular Temperature Transmitter TMT82

The TMT82 is a 2-wire temperature transmitter with dual universal sensor inputs, 2kV electrical isolation, supporting RTD, TC, Ohm, and mV, with drift detection and sensor backup, optionally SIL2/3.

  • Certification: AA-Non-hazardous area; BA-ATEX II1G Ex ia IIC T4/T5/T6
  • Communication and Output: A-HART; 1x 4-20 mA
  • Electrical Connection: 1-Spring terminals; 2-Screw terminals
  • Field Housing: A-None, DIN standard mounting kit
  • Universal Input Configuration: C1-Ch1: RTD 4-wire, Ch2: inactive; D2-Ch1: TC, Ch2: TC
  • Sensor Type Input 1: A1-Pt100; TK-Type K
  • Sensor Type Input 2: AA-Inactive; TK-Type K
  • Input Interconnection: A1-PV=CH1; CH2 inactive; A2-PV=CH1; SV=CH2
  • Additional Certification: LA-SIL compliance
  • Marking: Z2-device tag; Z4-fieldbus tag; ZA-descriptor tag

Modular Temperature Transmitter TMT84

The TMT84 is a PROFIBUS PA temperature transmitter with dual sensor inputs, advanced diagnostics, 2kV electrical isolation, and current consumption of 11mA.

  • Certification: A1-Non-hazardous area; B1-ATEX II1G Ex ia IIC T4/T5/T6
  • Output Signal: A-PROFIBUS PA
  • Electrical Connection: 1-Spring terminals; 2-Screw terminals
  • Field Housing: C-None
  • Configuration Input: C1-Ch1: RTD 4-wire, Ch2: inactive; D2-Ch1: TC, Ch2: TC
  • Firmware Version: 78-01.01.zz, PROFIBUS PA, Profile 3.02, DevRev02
  • Marking: Z2-device tag; Z4-fieldbus tag; Z5-bus address

Modular Temperature Transmitter TMT85

The TMT85 is a FOUNDATION Fieldbus temperature transmitter with dual sensor inputs, advanced diagnostics, 2kV electrical isolation, and current consumption of 11mA.

  • Certification: A1-Non-hazardous area; B1-ATEX II1G Ex ia IIC T4/T5/T6
  • Output Signal: A-FOUNDATION Fieldbus H1
  • Electrical Connection: 1-Spring terminals; 2-Screw terminals
  • Field Housing: C-None
  • Configuration Input: C1-Ch1: RTD 4-wire, Ch2: inactive; D2-Ch1: TC, Ch2: TC
  • Firmware Version: 77-02.00.zz, FF, DevRev02; 78-01.00.zz, FF, DevRev01
  • Marking: Z2-device tag; Z4-fieldbus tag; Z5-bus address

Selection Notes

  • Confirm the application environment and select the corresponding certification level (non-hazardous area or ATEX).
  • Select the appropriate sensor type and accuracy class according to the measuring range, accuracy, and vibration resistance requirements.
  • Determine the insertion length and diameter to ensure compatibility with existing equipment.
  • Select the transmitter model according to the communication protocol (HART, PROFIBUS PA, FOUNDATION Fieldbus).
  • Consider the required certificates and tests, such as material certificates, pressure tests, etc.

Conclusion

The MLTTS01 spare parts list provides a complete selection solution for temperature measurement spare parts. Through the structured information in this guide, users can quickly locate the required spare parts and ensure the accuracy and efficiency of system maintenance. Correct selection is key to ensuring the reliability of industrial process measurement.