In industrial process control, current simulation is a key operation for verifying the compatibility between flowmeter output signals and the control system. This article uses Endress+Hauser's Promag 53 electromagnetic flowmeter and Prosonic 93 ultrasonic flowmeter as examples to explain in detail the setup steps and precautions for current simulation. Mastering this method can effectively improve commissioning efficiency and reduce on-site troubleshooting time.

1. Basic Concepts of Current Simulation

Current simulation means that the instrument directly outputs a preset 4-20mA current value without relying on actual flow, and is used to test signal loops, PLC/DCS channels, valve positioners, etc. This function can simulate the minimum current (4mA), maximum current (20mA), or any intermediate value, helping technicians verify system linearity and response speed.

Both the Promag 53 and Prosonic 93 support this function, but the operation menus and parameter paths differ slightly. They are described separately below.

2. Promag 53 Current Simulation Operation Steps

2.1 Entering the Simulation Menu

  1. Ensure the instrument is in measurement mode, and press the "E" key to enter the main menu.
  2. Use the "+" or "-" key to select the "Diagnostics/Simulation" option, and press "E" to confirm.
  3. Select "Simulate Current Output", and press "E" to enter.

2.2 Setting the Simulation Value

  • Select "Simulation Value", and enter the target current (such as 4mA, 12mA, 20mA).
  • After pressing "E" to confirm, the instrument outputs the corresponding current and displays the current simulation status.
  • When exiting, select "End Simulation", and the instrument returns to normal output.

3. Prosonic 93 Current Simulation Operation Steps

3.1 Entering the Simulation Menu

  1. On the measurement screen, press the "E" key to enter the main menu.
  2. Select "Setup" → "Advanced Setup" → "Simulation".
  3. Select "Current Output Simulation", and press "E" to confirm.

3.2 Setting the Simulation Value

  • Enter the simulated current value (within the 4-20mA range), and press "E" to confirm.
  • The instrument immediately outputs that current and displays "Simulation Active".
  • Press "E" to exit or select "Cancel Simulation" to resume measurement.

4. Comparison of Current Simulation Parameters Between the Two Models

Item Promag 53 Prosonic 93
Menu Path Diagnostics/Simulation → Simulate Current Output Setup → Advanced Setup → Simulation → Current Output Simulation
Simulation Range 4-20mA (expandable to 3.8-22mA) 4-20mA
Accuracy ±0.05% full scale ±0.1% full scale
Exit Method Manually end simulation Manually cancel simulation

5. Common Issues and Precautions

  • No simulation output: Check whether the instrument is in the "Simulation Active" state and whether the output loop is disconnected.
  • Large current deviation: Confirm whether the load resistance is within the allowable range (usually ≤500Ω), and check the wiring terminals.
  • Unable to exit simulation: Try powering off and restarting, or check whether there is a higher-priority alarm.
  • Safety reminder: During simulation, the control system may receive false signals, so be sure to isolate in advance or notify relevant personnel.

6. Summary

Current simulation is an essential function for commissioning and maintenance of the Promag 53 and Prosonic 93. Through the above steps, technicians can quickly verify the signal loop and improve system reliability. It is recommended to record the original parameters before simulation and restore them promptly afterward to ensure process safety.