5L4C Product Overview

The 5L4C is an intelligent instrument widely used in industrial process control, supporting multiple input signals and output modes. Its core advantages lie in high precision, easy operation, and strong anti-interference capability, making it suitable for harsh industrial environments.

  • Input types: thermocouple, RTD, standard current/voltage
  • Output types: relay, SSR, 4-20mA
  • Display mode: dual-row four-digit LED digital tube
  • Power supply: AC/DC 85-265V or 24VDC

5L4C Selection Points

Selection by Signal Type

Select the corresponding input code according to the on-site sensor output signal to avoid measurement errors caused by signal mismatch.

  • Thermocouple: K, S, B, E, J, T, N, etc.
  • RTD: Pt100, Cu50, etc.
  • Analog quantity: 0-10V, 4-20mA, etc.

Selection by Control Output

Select the output module according to the actuator type. Common ones include relay output, solid-state relay drive, and linear current output.

5L4C Technical Parameters

Parameter ItemSpecification Description
Measurement accuracy±0.5% FS ±1 digit
Sampling period≤200ms
Working environmentTemperature 0-50℃, humidity ≤85%RH
Protection levelIP65 (front panel)
Installation methodPanel-mounted, opening size 45×45mm

5L4C Installation and Commissioning Steps

Installation Steps

  1. Cut a 45×45mm square hole on the panel, insert the instrument, and secure the clips.
  2. Connect the power, input, and output lines according to the wiring diagram in the manual.
  3. After confirming the wiring is correct, power on; the instrument will self-check and display the measured value.

Parameter Setting Steps

  1. Long press the SET key to enter the parameter menu.
  2. Use the up and down keys to modify input type, range, alarm value, etc.
  3. Press the SET key to save and exit; the instrument returns to normal operation.

Common Issues and Precautions

  • Abnormal display: Check whether the input signal exceeds the range or whether the wiring is loose.
  • Control not working: Confirm that the output type matches the actuator and whether the alarm value is set correctly.
  • Anti-interference: Use shielded cables for signal lines and keep them away from power lines.

For a more detailed 5L4C Chinese manual, please download this document and follow it. Correct selection and standardized installation can significantly improve system stability.