Mass Flow Meter 8A3C RS485 Version Manual Overview
This manual applies to the RS485 communication version of the 8A3C series mass flow meter and is intended for on-site commissioning engineers, system integrators, and procurement personnel. The document covers communication parameters, wiring definitions, register mapping, and key installation and commissioning points, and can be used together with the original PDF.

Click the icon above to download the Mass Flow Meter 8A3C Chinese Manual RS485 Version.pdf. It is recommended to read through the communication and wiring chapters before configuration.
RS485 Communication Core Parameters
Default Communication Settings
The 8A3C uses the Modbus RTU protocol by default at the factory. The parameters are shown in the table below. When connecting to a PLC or DCS on site, please verify these parameters first.
| Parameter | Default Value | Adjustable Range |
|---|---|---|
| Communication Protocol | Modbus RTU | Modbus RTU / ASCII |
| Baud Rate | 9600 bps | 1200~115200 bps |
| Data Bits | 8 bit | 7 / 8 bit |
| Stop Bits | 1 bit | 1 / 2 bit |
| Parity | None | None / Even / Odd |
| Slave Address | 1 | 1~247 |
Communication Cable and Termination Resistor
- It is recommended to use shielded twisted pair with a conductor cross-section of no less than 0.5 mm², and the shield should be grounded at one end only.
- When the bus length exceeds 100 m or the baud rate is higher than 38400 bps, a 120 Ω termination resistor should be installed at both ends of the bus.
- Use daisy-chain topology and avoid star branches. The branch length is recommended to be less than 1 m.
Wiring Definitions and Terminal Description
RS485 Terminal Assignment
The 8A3C transmitter usually provides dedicated communication terminals. Before wiring, confirm that the power supply is disconnected and check the terminal markings.
| Terminal Marking | Function | Description |
|---|---|---|
| A (D+) | RS485 differential positive | Connect to the A terminal of the host computer or gateway |
| B (D-) | RS485 differential negative | Connect to the B terminal of the host computer or gateway |
| GND | Communication ground | Optional; recommended for long-distance connections |
Wiring Steps
- Cut off the instrument power supply and confirm on-site safety.
- Connect the A and B wires of the shielded twisted pair to the corresponding terminals respectively, avoiding reverse connection.
- Ground the shield at one end on the control cabinet side, and leave the instrument side floating.
- Check whether the termination resistors at both ends of the bus match.
- After power-on, use debugging software to scan the slave address and confirm normal communication.
Register Mapping and Data Reading
Common Register Addresses
The process variables and configuration parameters of the 8A3C are distributed in holding registers. Pay attention to the data type and byte order when reading.
| Register Address | Name | Data Type | Unit |
|---|---|---|---|
| 0x0000 | Instantaneous mass flow value | Float32 | kg/h |
| 0x0002 | Total mass flow | Float32 | kg |
| 0x0004 | Medium temperature | Float32 | ℃ |
| 0x0006 | Medium density | Float32 | kg/m³ |
| 0x0010 | Slave address | UInt16 | — |
Notes on Data Reading
- Float32 uses big-endian byte order by default. If the host computer displays abnormally, try swapping the high and low words.
- For total flow, it is recommended to read regularly and perform power-off retention verification.
- Before writing registers, confirm the slave address and permissions to avoid accidental modification of the configuration.
Installation, Commissioning, and Troubleshooting
Pre-Commissioning Checklist
- The power supply voltage matches the nameplate, and grounding is reliable.
- The sensor installation direction is consistent with the flow direction arrow, and the upstream and downstream straight pipe sections meet the requirements.
- The RS485 A/B wires are not reversed, and the termination resistor configuration is correct.
- The host computer baud rate, parity, and slave address match those of the instrument.
Common Communication Faults
- No response: Check the slave address, baud rate, and A/B line polarity.
- Garbled data: Verify the parity and stop bits, and check the byte order.
- Intermittent communication: Check shield grounding, termination resistors, and bus branches.
- Value fluctuation: Confirm whether the medium is full in the pipe and whether vibration or electromagnetic interference exists.
Document Download and Technical Support
For complete parameters, register tables, and certification information, please refer to the Mass Flow Meter 8A3C Chinese Manual RS485 Version.pdf. When selecting and purchasing, please specify the communication version, nominal diameter, medium, and range so that the manufacturer can pre-configure the device.