VEGAPULS C 22 Radar Level Transmitter Overview

VEGAPULS C 22 is a compact radar level transmitter launched by VEGA, suitable for continuous level measurement of liquids and bulk solids. It uses 80 GHz high-frequency technology and features a small beam angle and strong anti-interference capability, making it especially suitable for installation in small tanks or narrow spaces.

This article provides the download of the VEGAPULS C 22 Chinese manual and explains selection, installation, commissioning, and maintenance, targeting engineering technical personnel and procurement personnel.

VEGAPULS C 22 Chinese Manual Download

Core Technology and Main Parameters

VEGAPULS C 22 is based on the 80 GHz frequency modulated continuous wave (FMCW) principle, with measurement accuracy up to ±2 mm. Its housing protection rating is IP66/IP67, suitable for harsh industrial environments.

Key Performance Parameters

ParameterValue
Measuring range0 ~ 15 m
Measurement accuracy±2 mm
Frequency80 GHz
Beam angleApprox. 8°
Process temperature-40 ~ +80 °C
Process pressure-1 ~ +3 bar
Output signal4 ~ 20 mA / HART
Protection ratingIP66/IP67

Installation and Commissioning Steps

Correct installation and commissioning are key to ensuring the measurement stability of the VEGAPULS C 22. The following steps are applicable to most conventional working conditions.

Installation Points

  • The installation location should avoid the feed inlet, agitator, and tank wall to prevent false echoes.
  • The instrument axis should be perpendicular to the material surface, and the tilt angle is recommended to be less than 3°.
  • For flange installation, ensure that the antenna extends beyond the flange surface to avoid nozzle reflection.
  • When used outdoors or in humid environments, it is recommended to install a protective cover.

Commissioning Steps

  1. Power on and confirm that the instrument self-test passes and the output current is within the 4 ~ 20 mA range.
  2. Connect the instrument via VEGADIS 81 or PC software PACTware.
  3. Enter the empty tank height (E value) and full tank height (F value), and set the measuring range.
  4. Execute the false echo suppression function and record the interference echo curve.
  5. Observe whether the level display matches the actual situation, and fine-tune parameters if necessary.

Common Problems and Maintenance Recommendations

VEGAPULS C 22 is usually maintenance-free, but in high-dust or scaling-prone working conditions, the antenna surface needs to be checked regularly.

  • Fluctuating measured value: Check whether there is interference from an agitator or feed flow, and re-execute false echo suppression.
  • No signal output: Confirm whether the supply voltage and loop load are within the allowable range.
  • Antenna scaling: Wipe with a soft cloth and neutral detergent, avoiding scratching the lens.

For complete wiring diagrams, dimension drawings, and fault code tables, please download the VEGAPULS C 22 Chinese manual for reference.

VEGAPULS C 22 Chinese Manual Download

Selection and Procurement Recommendations

When purchasing VEGAPULS C 22, it is necessary to confirm the process connection, output signal, and certification requirements. Common options include:

  • Process connection: G1½ thread, flange, etc.
  • Output: 4 ~ 20 mA / HART.
  • Certification: ATEX, IECEx, and other explosion-proof certifications (depending on working conditions).

It is recommended to provide the supplier with the medium name, temperature, pressure, and measuring range to quickly match the model.