VEGATOR 111 Chinese Manual Download

VEGATOR 111 is a level switch controller launched by VEGA, commonly used for limit detection and pump control. To facilitate on-site commissioning and maintenance, we provide the official Chinese manual PDF download. Click the link below to get the complete document.

VEGATOR 111 Chinese Manual PDF Download Download VEGATOR 111 Chinese Manual.pdf

VEGATOR 111 Product Overview

VEGATOR 111 is a controller for level limit detection and can be used with various level switches. It realizes alarm or pump control through relay output and is widely used in water treatment, chemical, food, and other industries.

Main Functions

  • Supports two-point limit detection (e.g., high and low levels)
  • Relay output, configurable as normally open/normally closed
  • Adjustable delay to avoid false triggering
  • Compact design, DIN rail mounting

Technical Parameters and Selection

The following are the key technical parameters of VEGATOR 111 for reference by engineering technicians and procurement.

ParameterValue
Supply voltage24 V DC or 230 V AC
Output2 relay outputs
Contact capacity250 V AC / 2 A
Protection classIP20 (terminals)
Operating temperature-20 … +60 °C
Mounting methodDIN rail

Wiring and Commissioning Steps

Correct wiring and commissioning are key to ensuring stable operation of VEGATOR 111. Please follow the steps below.

  1. Confirm that the supply voltage matches the instrument nameplate and disconnect the power supply.
  2. Connect the level switch signal wires to the corresponding terminals according to the manual.
  3. Connect the relay output to the alarm or pump controller.
  4. After power-on, set the delay and sensitivity via potentiometer or DIP switch.
  5. Perform a simulation test to observe whether the relay operates normally.

Common Problems and Precautions

Common Problems

  • Relay does not operate: Check the power supply, signal input, and delay settings.
  • False alarm: Adjust sensitivity or increase delay.
  • Unable to calibrate: Confirm that the level switch type matches the controller.

Precautions

  • Keep away from strong electromagnetic interference sources during installation.
  • Wiring must comply with local electrical codes.
  • Regularly check terminal tightness and housing cleanliness.

Summary

VEGATOR 111 is a reliable level limit controller. Together with VEGA level switches, it enables precise limit detection and pump control. Downloading the Chinese manual provides complete wiring diagrams, parameter tables, and commissioning guidelines to help rapid on-site startup.