Instrumentation · Engineering · Package · PLC
0755-8222 1901 sales@ainstru.com

PMD75 differential pressure transmitter

PMD75 differential pressure transmitter

Deltabar S PMD75

Configurable Models 5 models
The differential pressure transmitter adopts a metal sensor for differential pressure measurement.
Compare

Continuous / Liquids

Measuring Principle Differential pressure
Characteristic / Application Digital transmitter with metallic measuring diaphragms
Modular transmitter
Long term stability
High static pressure/Overload resistance
Enhanced safety via self diagnostic functions
Secondary process barrier
Supply / Communication 4...20 mA HART:
10,5...45V DC
Ex ia: 10,5...30V DC
PROFIBUS PA /
FOUNDATION Fieldbus:
9...32V DC
Accuracy Standard: 0.05%
Platinum: up to 0.035%
Long term stability 0,05% of URL/year
Ambient temperature -50 °C...85 °C
(-58 °F...185 °F)
Process temperature -40 °C...85 °C
(-40 °F...185 °F)
Process pressure / max. overpressure limit 420 bar (6300 psi)
Pressure measuring range 10 mbar...250 bar
(0.15 psi...3750 psi)
Main wetted parts Alloy C276
316L
Monel
Tantalum
Process connection 1/4-18NPT
RC1/4"
Max. measurement distance 400 m (1.312 ft) H2O
Communication 4...20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
Certificates / Approvals ATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI, EAC
Safety approvals SIL
Design approvals EN 10204-3.1
NACE MR0175, MR0103
Marine approval GL/ ABS
Options HistoROM/M-Dat
4-line digital display
SS- or Aluminiumhousing
Separate housing
Successor PMD75B
Application limits Measuring cell:
Metal welded

Gas

Measuring Principle Differential pressure
Product headline Digital transmitter with metallic measuring diaphragms
Modular transmitter
Long-term stability
High static pressure/Overload resistance
Enhanced safety via self diagnostic functions
Secondary process barrier
Max. measurement error 0,075%
"PLATINUM" 0,05%
Max. process pressure max. 420 bar
(max. 6 091 psi)
Medium temperature range Temperature gradient from pressure piping
Display/Operation Option
Outputs 4...20mA HART
PROFIBUS PA
FOUNDATION Fieldbus
Digital communication HART
PROFIBUS PA
FOUNDATION Fieldbus
Hazardous area approvals ATEX, FM, CSA, IECEx, INMETRO, NEPSI, TIIS
Functional safety SIL
Material certificates NACE MR0103
NACE MR0175
EN10204-3.1

Liquids

Measuring Principle Differential pressure
Product headline Digital transmitter with metallic measuring diaphragms
Modular transmitter
Long-term stability
High static pressure/Overload resistance
Enhanced safety via self diagnostic functions
Secondary process barrier
Max. measurement error 0,075%
"PLATINUM" 0,05%
Max. process pressure max. 420 bar
(max. 2175 psi)
Medium temperature range Temperature gradient from pressure piping
Display/Operation Option
Outputs 4...20mA HART
PROFIBUS PA
FOUNDATION Fieldbus
Digital communication HART
PROFIBUS PA
FOUNDATION Fieldbus
Hazardous area approvals ATEX, FM, CSA, IECEx, INMETRO, NEPSI, TIIS
Functional safety SIL
Material certificates NACE MR0103
NACE MR0175
EN10204-3.1

Pressure

Measuring Principle Differential pressure
Characteristic Digital transmitter with metallic measuring diaphragms
Modular transmitter
Long-term stability
High static pressure/Overload resistance
Secondary process barrier
Supply voltage 4...20 mA HART
10,5...45V DC (Non Ex):
Ex ia: 10,5...30V DC
PROFIBUS PA:
9...32 V DC (Non Ex)
FOUNDATION Fieldbus:
9...32 V DC (Non Ex)
Reference Accuracy Standard: 0.05%
Platinum: up to 0.035%
Long term stability 0.03 % of URL/ year
0.05 % of URL/ 5 years
0.08 % of URL/ 10 years
Process temperature -40°C...85°C
(-40°F...185°F)
Ambient temperature -50°C...85°C
(-58°F...185°F)
Measuring cell 10 mbar...250 bar
(0.15 psi...3750 psi)
Smallest calibratable span 1 mbar (0.015 psi)
Vacuum resistance 50 mbar (0.73 psi)
Max. Turn down 100:1
Max. overpressure limit On one side:
420 bar
(6300psi)
Process connection 1/4-18NPT
RC1/4"
Material process membrane 316L, AlloyC,
Tantal,
Gold-Rhodium
Material gasket Viton, PTFE, EPDM, NBR
Fill fluid Silicone oil
Inert oil
Material housing 316L, Die-cast aluminum
Communication 4...20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
Certificates / Approvals ATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI, EAC, UK Ex
Safety approvals SIL
Design approvals NACE MR0103
EN10204-3.1
Marine approvals GL/ ABS
Specialities Diagnostic functions
Successor PMD75B

Steam

Measuring Principle Differential pressure
Product headline Digital transmitter with metallic measuring diaphragms
Modular transmitter
Long-term stability
High static pressure/Overload resistance
Enhanced safety via self diagnostic functions
Secondary process barrier
Max. measurement error 0,075%
"PLATINUM" 0,05%
Max. process pressure max. 420 bar
(max. 6091 psi)
Medium temperature range Temperature gradient from pressure piping
Display/Operation Option
Outputs 4...20mA HART
PROFIBUS PA
FOUNDATION Fieldbus
Digital communication HART
PROFIBUS PA
FOUNDATION Fieldbus
Hazardous area approvals ATEX, FM, CSA, IECEx, INMETRO, NEPSI, TIIS
Functional safety SIL
Material certificates NACE MR0103
NACE MR0175
EN10204-3.1

Areas of application
The Deltabar PMD75 differential pressure transmitter with piezoresistive sensor and welded metal diaphragm is used for the continuous measurement of liquids, steam and gases in all industries. Three-key operation enables simple and reliable commissioning and operation. The integrated HistoROM data module allows easy management of process and device parameters. Designed according to IEC 61508 for SIL2/3 safety applications.
For level, volume or mass measurement of liquids, differential pressure monitoring, and flow measurement (volume or mass flow) together with primary elements in gases, steam and liquids.
Process connection: thread
Process temperature: -40 to +85°C (-40 to +185°F)
Measuring range: 0.25mbar to 40bar (0.0036 to 600psi)
Accuracy: ±0.05%, “platinum” ±0.035% (optional)
International explosion protection certificate, overflow protection WHG, SIL, hygienic approval, marine approval

Advantages
Optimum accuracy, reproducibility and long-term stability
Certified to IEC 61508, hermetically sealed feedthrough provides the highest SIL2/3 safety
Simple menu-guided commissioning via local display, 4 to 20mA HART, PROFIBUS PA, FOUNDATION fieldbus
HistoROM data management concept for fast and easy commissioning, maintenance and diagnostics
Cost savings through the modular concept, easy replacement of sensor, display or electronics
Overload resistance up to 420bar/42MPa/6300psi, function monitored
Seamless and independent system integration (HART/PA/FF)

 

E+H Product Configurator

Please enter the product order code to configure

Product comparison

Please enter the order codes of the products to compare in the boxes below (up to three products)

 

Technical documentation

   

Technical data

 

 

Documents/Manuals/Software

 

 

Accessories/Spare parts

 

   

Orifice plate flowmeter measuring principle video

   

Pitot tube flowmeter measuring principle video

Source:Endress+Hauserwebsite public information

Model Name
PMD75-ABJ7HE1DCBA 差压变送器
PMD75-5CG7DE1DCAU+JTL8 差压变送器
PMD75-5BA7F11DAAA+N5PJ 差压变送器
PMD75-HCA7L21BAEU 差压变送器
PMD75-ACA7BB1DAUA 差压变送器
Municipal Wastewater Treatment

Municipal Wastewater Treatment — Wastewater Treatment Plant · Differential Pressure Measurement Application Case

Project Background

Municipal Wastewater Treatment customers at the Wastewater Treatment Plant stage have long faced the challenge of insufficient accuracy in effluent quality monitoring and instruments prone to contamination causing data drift, affecting compliance discharge, placing higher demands on the stability and measurement accuracy of Differential Pressure Measurement.

Solution

Based on the on-site conditions, the Ainstru technical team selected suitable Differential Pressure Measurement for the customer and delivered one-stop service covering selection, installation, commissioning and tuning.

Results

  • Measurement accuracy and response speed significantly improved, with stable and reliable data;
  • Instruments adapt to complex Municipal Wastewater Treatment conditions, greatly reducing maintenance;
  • Helping customers achieve continuous online monitoring and cost reduction, highly recognized by customers.
Food & Beverage

Food & Beverage — Food Production Line · Differential Pressure Measurement Application Case

Project Background

Food & Beverage customers at the Food Production Line stage have long faced the challenge of high hygienic measurement requirements, with inline instruments needing to withstand CIP/SIP cleaning while maintaining stable accuracy, placing higher demands on the stability and measurement accuracy of Differential Pressure Measurement.

Solution

Based on the on-site conditions, the Ainstru technical team selected suitable Differential Pressure Measurement for the customer and delivered one-stop service covering selection, installation, commissioning and tuning.

Results

  • Measurement accuracy and response speed significantly improved, with stable and reliable data;
  • Instruments adapt to complex Food & Beverage conditions, greatly reducing maintenance;
  • Helping customers achieve continuous online monitoring and cost reduction, highly recognized by customers.
Chemical & Pharmaceutical

Chemical & Pharmaceutical — Reactors and Storage Tanks · Differential Pressure Measurement Application Case

Project Background

Chemical & Pharmaceutical customers at the Reactors and Storage Tanks stage have long faced the challenge of highly corrosive media and complex conditions, requiring corrosion-resistant and explosion-proof instruments, placing higher demands on the stability and measurement accuracy of Differential Pressure Measurement.

Solution

Based on the on-site conditions, the Ainstru technical team selected suitable Differential Pressure Measurement for the customer and delivered one-stop service covering selection, installation, commissioning and tuning.

Results

  • Measurement accuracy and response speed significantly improved, with stable and reliable data;
  • Instruments adapt to complex Chemical & Pharmaceutical conditions, greatly reducing maintenance;
  • Helping customers achieve continuous online monitoring and cost reduction, highly recognized by customers.
Power & Energy

Power & Energy — Power Plant Boiler and Turbine · Differential Pressure Measurement Application Case

Project Background

Power & Energy customers at the Power Plant Boiler and Turbine stage have long faced the challenge of unstable measurement under high temperature and pressure, with high maintenance and downtime costs, placing higher demands on the stability and measurement accuracy of Differential Pressure Measurement.

Solution

Based on the on-site conditions, the Ainstru technical team selected suitable Differential Pressure Measurement for the customer and delivered one-stop service covering selection, installation, commissioning and tuning.

Results

  • Measurement accuracy and response speed significantly improved, with stable and reliable data;
  • Instruments adapt to complex Power & Energy conditions, greatly reducing maintenance;
  • Helping customers achieve continuous online monitoring and cost reduction, highly recognized by customers.