Instrumentation · Engineering · Package · PLC
0755-8222 1901 sales@ainstru.com

TMT122 rail type temperature transmitter

TMT122 rail type temperature transmitter

iTEMP TMT122,Transmitter DINrail HART

Configurable Models 3 models
Convert sensor signals into stable standardized output signals suitable for all industries
Compare

Temperature transmitters

Measuring Principle
Input 1 x RTD, TC, Ohm, mV
Output 1 x analog 4...20 mA
Auxiliary power supply 12...35 V DC (standard-version)
12...30 V DC (Ex-version)
Communication HART-protocol
Installation DIN rail
Accuracy (Pt100, -50...200 °C) <= 0,2 K
(Pt100, -58...392 °F) <= 0,4 °F
Galvanic isolation yes
Certification UL rec. Comp
marine approval
GOST Metrology
FM IS,NI,Class I,Div.1+2,Group ABCD
CSA IS,NI,Class I,Div.1+2,Group ABCD
ATEX II2(1)G Ex ia[ia Ga] IIC T6 Gb
ATEX II3G Ex nA IIC T6
FM+CSA IS,NI,Class I,Div.1+2,Group ABCD
CSA General Purpose
IECEx Ex ia IIC T6/T5/T4
NEPSI Ex nA IIC T4-T6

Superior reliability, accuracy and long-term stability in critical processes in all industries. The configurable transmitter not only digitally converts resistance thermometer (RTD) and thermocouple (TC) signals, but can also convert resistance and voltage signals via HART® communication. Commissioning tools installed on a personal computer enable fast, simple operation, display and maintenance. Mounted on a DIN rail complying with IEC 60715 (housing width: 22.5 mm).

 

Advantages

Universal configuration via HART® communication

High-precision measurement over the entire ambient temperature range

Fault signal on sensor wire break or short circuit, in accordance with NAMUR NE43

Meets EMC requirements in accordance with NAMUR NE21, CE approval

Explosion protection certificates: ATEX Ex, CSA IS, FM IS

Galvanic isolation

Complies with SIL2 approval

 

Application areas

The HART® communication temperature transmitter is used to convert different input signals into a 4...20 mA analog output signal

Input: resistance thermometer (RTD), thermocouple (TC), resistance (Ω) and voltage (mV)

HART® communication, operating front-end or panel devices using a handheld (DXR275, DXR375) or personal computer (e.g. ReadWin 2000 or FieldCare)

 

 

E+H Product Model Configurator

Please enter the product model to configure

Product comparison

Please enter the product models to compare in the input fields below; up to three products can be compared

 

   

Technical documentation

   

Technical data

 

 

Documents / Manuals / Software

 

 

Accessories / Spare parts

 

Source:Endress+Hauserpublic information from the website

Model Name
TMT122-A1KBA 导轨式温度变送器
TMT122-ACKBA 导轨式温度变送器
TMT122-131AA 导轨式温度变送器
Municipal Wastewater Treatment

Municipal Wastewater Treatment — Wastewater Treatment Plant · Temperature Transmitter Application Case

Project Background

Municipal Wastewater Treatment customers at the Wastewater Treatment Plant stage have long faced the challenge of insufficient accuracy in effluent quality monitoring and instruments prone to contamination causing data drift, affecting compliance discharge, placing higher demands on the stability and measurement accuracy of Temperature Transmitter.

Solution

Based on the on-site conditions, the Ainstru technical team selected suitable Temperature Transmitter for the customer and delivered one-stop service covering selection, installation, commissioning and tuning.

Results

  • Measurement accuracy and response speed significantly improved, with stable and reliable data;
  • Instruments adapt to complex Municipal Wastewater Treatment conditions, greatly reducing maintenance;
  • Helping customers achieve continuous online monitoring and cost reduction, highly recognized by customers.
Food & Beverage

Food & Beverage — Food Production Line · Temperature Transmitter Application Case

Project Background

Food & Beverage customers at the Food Production Line stage have long faced the challenge of high hygienic measurement requirements, with inline instruments needing to withstand CIP/SIP cleaning while maintaining stable accuracy, placing higher demands on the stability and measurement accuracy of Temperature Transmitter.

Solution

Based on the on-site conditions, the Ainstru technical team selected suitable Temperature Transmitter for the customer and delivered one-stop service covering selection, installation, commissioning and tuning.

Results

  • Measurement accuracy and response speed significantly improved, with stable and reliable data;
  • Instruments adapt to complex Food & Beverage conditions, greatly reducing maintenance;
  • Helping customers achieve continuous online monitoring and cost reduction, highly recognized by customers.
Chemical & Pharmaceutical

Chemical & Pharmaceutical — Reactors and Storage Tanks · Temperature Transmitter Application Case

Project Background

Chemical & Pharmaceutical customers at the Reactors and Storage Tanks stage have long faced the challenge of highly corrosive media and complex conditions, requiring corrosion-resistant and explosion-proof instruments, placing higher demands on the stability and measurement accuracy of Temperature Transmitter.

Solution

Based on the on-site conditions, the Ainstru technical team selected suitable Temperature Transmitter for the customer and delivered one-stop service covering selection, installation, commissioning and tuning.

Results

  • Measurement accuracy and response speed significantly improved, with stable and reliable data;
  • Instruments adapt to complex Chemical & Pharmaceutical conditions, greatly reducing maintenance;
  • Helping customers achieve continuous online monitoring and cost reduction, highly recognized by customers.
Power & Energy

Power & Energy — Power Plant Boiler and Turbine · Temperature Transmitter Application Case

Project Background

Power & Energy customers at the Power Plant Boiler and Turbine stage have long faced the challenge of unstable measurement under high temperature and pressure, with high maintenance and downtime costs, placing higher demands on the stability and measurement accuracy of Temperature Transmitter.

Solution

Based on the on-site conditions, the Ainstru technical team selected suitable Temperature Transmitter for the customer and delivered one-stop service covering selection, installation, commissioning and tuning.

Results

  • Measurement accuracy and response speed significantly improved, with stable and reliable data;
  • Instruments adapt to complex Power & Energy conditions, greatly reducing maintenance;
  • Helping customers achieve continuous online monitoring and cost reduction, highly recognized by customers.