Key Points for Installation and Selection of E+H TST602 Surface Thermometer
The measurement accuracy of a surface thermometer is significantly affected by the installation method, especially the pipe diameter and whether it is installed flat against a surface. During the selection and procurement stage, the appropriate measurement module must be chosen according to the actual working conditions to ensure measurement accuracy and long-term stability.
Measurement Module Selection Rules
According to the E+H TST602 manual, measurement modules are divided into two types: curved and flat. The following rules must be strictly followed during selection:
- Curved module: Supports round pipe installation up to DN100.
- Flat module: Suitable for round pipes larger than DN100 or flat surface installation.
Incorrect selection may lead to poor contact between the sensor and the pipe wall, thereby affecting response speed and measurement accuracy.
Selection Comparison and Recommendations
To facilitate quick decision-making for engineering and procurement personnel, the following table summarizes module selection recommendations under different working conditions:
| Pipe Condition | Recommended Module Type | Remarks |
|---|---|---|
| Round pipe, DN≤100 | Curved module | Ensure the curvature fits the pipe wall |
| Round pipe, DN>100 | Flat module | Must be used with mounting clamps |
| Flat surface (e.g., flat plate, tank wall) | Flat module | Install directly against the surface |
Correct selection can effectively improve the repeatability and reliability of temperature measurement and avoid additional maintenance costs caused by improper installation.