CPS91D Chinese Manual Download

You can directly download the complete CPS91D Chinese manual to obtain detailed technical specifications, wiring diagrams, and operation instructions. This manual is an important reference for on-site installation and commissioning.

CPS91D Chinese Manual PDF Download Download CPS91D Chinese Manual.pdf

CPS91D Product Overview

CPS91D is an instrument widely used in industrial process control, featuring high precision and stability. It is typically used for measurement and transmission of parameters such as pressure, liquid level, or temperature.

This product is suitable for automation systems in petroleum, chemical, power, water treatment, and other industries. Its design meets the requirements of industrial sites for protection rating and anti-interference capability.

Core Technical Parameters

Main Performance Indicators

Parameter Item Typical Value Remarks
Measurement Range 0~10 MPa Customizable
Output Signal 4~20 mA / HART Two-wire
Power Supply 12~36 VDC Typical 24V
Accuracy Class ±0.1% FS Refer to manual
Protection Rating IP67 Suitable for outdoor

Electrical and Mechanical Characteristics

  • Process Connection: G1/2, M20×1.5 and other standard threads
  • Diaphragm Material: 316L stainless steel, Hastelloy, etc. optional
  • Ambient Temperature: -40~85℃
  • Medium Temperature: -40~125℃ (higher with heat sink)

Installation and Wiring Guide

Installation Steps

  1. Confirm that the pipeline or container has been depressurized and close the valve.
  2. According to the process connection specification, wrap PTFE tape or use a gasket.
  3. Screw the CPS91D into the installation point and tighten with a wrench, avoiding excessive force that may damage the housing.
  4. Ensure the cable entry faces downward or sideways to prevent water accumulation.
  5. Connect the power and signal lines according to the wiring diagram in the manual, paying attention to polarity.

Wiring Precautions

  • Use shielded cables, with the shield grounded at one end.
  • Avoid parallel routing with power cables to reduce electromagnetic interference.
  • Before power-on, check whether the power supply voltage is within the 12~36 VDC range.

Selection and Ordering Information

When selecting, it is necessary to specify the measurement range, process connection, output signal, diaphragm material, and whether a display head is included. Different options correspond to different model codes; please refer to the selection table in the manual.

For special ranges or explosion-proof certification, please confirm with the supplier. Correct selection ensures that CPS91D operates stably for a long time under your working conditions.

Common Problems and Maintenance

Common Problems

  • No output signal: Check power polarity, voltage, and whether wiring is loose.
  • Output fluctuation: Confirm whether the medium is pulsating, or increase damping setting.
  • Zero drift: Recalibrate the zero point and check for overpressure or overtemperature.

Daily Maintenance

  • Regularly check appearance and sealing, and clean the housing.
  • Perform calibration every 12 months to ensure accuracy.
  • Avoid use beyond the rated pressure or temperature range.

The above content is based on the CPS91D Chinese manual. For detailed technical data, please refer to the official PDF file.