You can directly click the link below to download the complete FTL41 Chinese manual (PDF format). This manual covers product introduction, technical specifications, installation guide, operating instructions, and troubleshooting, and is an essential document for on-site commissioning and maintenance.
Download FTL41 Chinese Manual.pdf
FTL41 Product Overview
FTL41 is a capacitive level transmitter used for continuous level measurement, widely used for liquid level or material level detection of liquids, slurries, and granular solids. It adopts advanced capacitive sensing technology and can adapt to high-temperature, high-pressure, and corrosive working conditions.
The instrument outputs a 4-20mA standard signal and optionally supports the HART communication protocol, making it easy to integrate into DCS or PLC systems. With its high precision, stability, and ease of use, the FTL41 has become an ideal choice in industrial process control.
FTL41 Technical Parameters
The following are the main technical specifications of the FTL41 for selection and procurement reference. For detailed parameters, please refer to the Chinese manual.
| Parameter Item | Specification Description |
|---|---|
| Measurement Principle | Capacitive |
| Measurement Range | 0~20m (depending on medium) |
| Accuracy | ±0.5% FS |
| Output Signal | 4-20mA / HART |
| Process Connection | G1/2, G1, flange (optional) |
| Process Temperature | -40~+200℃ |
| Process Pressure | -1~+40bar |
| Protection Rating | IP67 |
| Power Supply | 24V DC |
FTL41 Installation and Commissioning
Installation Precautions
- The installation position should avoid the feed inlet and agitator to prevent false echoes.
- Ensure sufficient distance between the probe and the vessel wall to avoid capacitive coupling interference.
- For adhesive media, it is recommended to use a probe with a shielded section or clean it regularly.
- When used in explosive hazardous areas, intrinsically safe or explosion-proof types must be selected and relevant regulations must be followed.
Commissioning Steps
- After power-on, check whether the instrument displays normally (if equipped with LCD) or whether the output current is around 4mA.
- Enter the parameter setting menu and select the medium type (liquid/solid) and measurement range.
- Perform empty tank calibration (4mA point) and full tank calibration (20mA point).
- If necessary, adjust the damping time to stabilize the output.
- Save the settings and exit, and observe whether the output changes linearly with the level.
For detailed commissioning menus and fault codes, please refer to the FTL41 Chinese manual.
FTL41 Selection Guide
Correct selection is the key to ensuring measurement performance. Please determine the model according to the following factors:
- Medium Characteristics: dielectric constant, corrosiveness, adhesiveness, whether it is prone to crystallization.
- Process Conditions: temperature, pressure, vacuum degree.
- Installation Method: thread, flange, clamp, etc.
- Output and Communication: 4-20mA, HART, switching value, etc.
- Certification Requirements: explosion-proof, sanitary, classification society, etc.
If you need more detailed selection codes, please download the selection table in the FTL41 Chinese manual.
Common Problems and Maintenance
Common Fault Handling
- Output always at 4mA: Check whether the probe is scaled or the dielectric constant of the medium is too low.
- Large output fluctuation: Increase the damping time and check whether the grounding is good.
- No output: Check the power supply and wiring polarity.
Daily Maintenance
- Regularly check the probe for damage or corrosion.
- Clean attachments on the probe surface, especially for viscous media.
- Perform calibration verification every six months.
For more maintenance details, please refer to the FTL41 Chinese manual.