FMR67B Radar Level Transmitter Overview

FMR67B is a high-performance radar level transmitter launched by Endress+Hauser, based on 80 GHz frequency modulated continuous wave (FMCW) technology, suitable for continuous level measurement of liquids and bulk solids. Its compact design and extremely high measurement accuracy make it widely used in chemical, petrochemical, water treatment, and food industries.

This article provides the download entry for the FMR67B Chinese manual and systematically organizes its technical parameters, installation points, and selection considerations, making it convenient for engineering technicians and procurement personnel to quickly consult.

FMR67B Chinese Manual Download

Click the link below to obtain the complete FMR67B Chinese manual PDF file, covering safety guidelines, electrical connections, commissioning steps, and troubleshooting.

FMR67B Chinese Manual PDF DownloadDownload FMR67B Chinese Manual.pdf

Core Technical Parameters

The main technical parameters of the FMR67B are shown in the table below for reference during selection and configuration.

Parameter Value/Description
Measurement principle 80 GHz FMCW radar
Measuring range Max. 30 m (liquid), max. 15 m (solid)
Accuracy ±2 mm
Process temperature -40 … +200 °C
Process pressure -1 … +40 bar
Output signal 4…20 mA HART, PROFIBUS PA, FOUNDATION Fieldbus
Protection class IP66/68 (NEMA 4X/6P)

Installation and Commissioning Points

Installation Precautions

  • Ensure the antenna axis is perpendicular to the material surface and avoid installation directly above the feed inlet.
  • For liquid measurement, it is recommended to use a lens antenna or horn antenna, and keep the distance between the antenna end and the highest level not less than the blind zone.
  • In working conditions with stirring or foam, a still pipe or bypass pipe installation method should be selected.
  • Avoid installation near obstacles in the tank (such as heating coils, baffles) to prevent false echoes.

Commissioning Steps

  1. Connect the instrument via a HART handheld communicator or Endress+Hauser's FieldCare/DeviceCare software.
  2. Set the empty tank calibration (E point) and full tank calibration (F point).
  3. Select the dielectric constant range according to the medium characteristics and enable the echo suppression function.
  4. Check the echo curve to confirm that the main echo is at the expected position and its amplitude is stable.
  5. Save the parameters and record the commissioning report.

Common Problems and Selection Recommendations

Common Problems

  • Fluctuating measured value: Check whether the antenna is scaled, or whether the medium generates foam or steam.
  • Signal loss: Confirm whether the supply voltage and loop resistance are within the allowable range.
  • False echoes: Use the echo suppression curve to eliminate fixed interference.

Selection Recommendations

  • For high-temperature and high-pressure conditions, choose the version with a high-temperature isolation flange.
  • For corrosive media, choose a PTFE or ceramic sealed antenna.
  • For sanitary applications, choose 3-A or EHEDG certified clamp connections.

Summary

With its 80 GHz technology, high accuracy, and rich communication interfaces, the FMR67B radar level transmitter has become a reliable choice for industrial level measurement. Correctly downloading and reading the Chinese manual, combined with the parameter analysis and installation recommendations in this article, can significantly improve commissioning efficiency and measurement stability.