FMR62 Chinese Manual Download
You can directly download the FMR62 Chinese manual (PDF format) to obtain complete installation, commissioning, and maintenance guidance.
Download FMR62 Chinese Manual.pdf
FMR62 Product Overview
FMR62 is an 80GHz radar level meter launched by Endress+Hauser (E+H). It adopts a non-contact measurement principle and is suitable for liquid and solid level measurement. Its core advantages include high precision, small beam angle, and strong anti-interference capability.
Main Technical Parameters
| Parameter | Value |
|---|---|
| Measurement principle | 80GHz frequency modulated continuous wave (FMCW) |
| Measurement range | Maximum 40 meters (liquid), maximum 30 meters (solid) |
| Measurement accuracy | ±1mm |
| Process temperature | -40°C ~ +200°C |
| Process pressure | -1 ~ +40 bar |
| Output signal | 4-20mA HART / PROFIBUS PA / FOUNDATION Fieldbus |
| Protection class | IP66/67, NEMA 4X |
Selection Points
Correct selection is the prerequisite for ensuring the stable operation of FMR62. Attention should be paid to the following aspects:
- Process connection: Select according to on-site flange standards (such as DN50 PN16, ANSI 2" 150lb).
- Antenna type: PTFE horn antenna is standard; fully sealed antenna is optional for corrosive media.
- Output mode: Select 4-20mA HART or bus protocol according to the control system.
- Certification requirements: Intrinsically safe or explosion-proof type is required for hazardous areas.
Installation and Commissioning Steps
Please strictly follow the steps below to ensure measurement accuracy:
- Confirm the installation position: avoid interference sources such as feed inlets and agitators, and keep the antenna perpendicular to the material surface.
- Fix the instrument: use a suitable flange or threaded connection to ensure good sealing.
- Electrical connection: connect the power and signal lines according to the wiring diagram in the manual, and pay attention to polarity.
- Power-on initialization: after the instrument self-check, set parameters through the local display or commissioning software.
- Empty tank calibration: perform empty spectrum suppression of false echoes in an empty tank state.
- Full tank calibration: input the actual level value to complete full span calibration.
Common Problems and Maintenance
- Fluctuating measured value: check for condensation, buildup, or agitation interference, and enable the echo threshold function.
- No signal output: confirm whether the supply voltage and loop resistance are normal.
- Regular maintenance: check antenna cleanliness every six months, and wipe with a soft cloth if necessary.