1. Installation Position

Correct installation position is crucial for measurement accuracy. Please ensure the flowmeter is installed in a location with a sufficiently long straight pipe section, and avoid vibration and strong electromagnetic interference.

Installation position diagram

2. Power Supply Requirements

The power supply voltage must match the voltage marked on the nameplate. Please be sure to check the nameplate information to avoid equipment damage caused by voltage mismatch.

Power supply nameplate diagram

2.1 Terminal Assignment

The electrical connection diagram of the terminals is located on the nameplate of the electronics module. Please wire correctly according to the diagram to ensure that the power supply and signal lines are connected properly.

Terminal diagram

3. Operation Menu

The operation menu is the main interface for parameter setting and viewing measured values. All configuration options can be accessed through the menu.

Operation menu diagram

3.1 Operation Display

The display provides real-time measured values and menu navigation information. Familiarity with the display interface helps to operate quickly.

Operation display diagram

3.2 Editing Diagram

The editing diagram shows the process of parameter modification. Please follow the steps in the diagram to edit parameters.

Editing diagram

4. Commissioning

Commissioning is a key step to ensure accurate measurement of the flowmeter. The following commissioning steps must be performed in order.

4.1 Setting the Operating Language

Factory setting: English or the local language ordered. The operating language can be changed as needed.

Setting language diagram

4.2 Setting the Measuring Device

The "Setup" menu and its setup wizard contain all parameters required for standard operation. Please configure them in sequence.

Setting measuring device diagram

4.3 Selecting Gas Type

Menu path: "Setup" menu → Select gas type. Select the correct gas according to the actual measuring medium.

Selecting gas type diagram

4.4 Setting Process Pressure

Menu path: "Setup" menu → Process pressure. Enter the actual process pressure value.

Setting process pressure diagram

4.5 Determining Installation Factor

Menu path: "Setup" menu → Installation factor. Set the appropriate factor according to the installation conditions.

Determining installation factor diagram

4.6 Setting Current Output

Menu path: "Setup" menu → Assign current output; "Setup" menu → 4 mA value; "Setup" menu → 20 mA value. Configure the current output range.

Setting current output diagram

4.7 Setting Pulse/Frequency/Switch Output

Menu path:

  • "Setup" menu → Operating mode
  • "Setup" menu → Assign frequency output
  • "Setup" menu → Switch output function
  • "Setup" menu → Assign pulse output
Setting pulse frequency output diagram 1 Setting pulse frequency output diagram 2