Prosonic 93 Simulated Current Output Overview

Prosonic 93 is an ultrasonic level meter from Endress+Hauser, widely used in industrial process measurement. Its simulated current output function allows users to simulate a 4-20 mA current signal without opening the cover, for loop testing and system commissioning.

For engineering and technical personnel and procurement personnel, this function is an important means of verifying whether the connection between the instrument and the control system is normal. Through simulated output, line faults can be quickly troubleshot, improving maintenance efficiency.

Prosonic 93 simulated current output interface

Operating Steps for Simulated Current Output

To enable the simulated current output of the Prosonic 93, follow the steps below. Please ensure the instrument is powered on and in normal working condition.

  1. Enter the instrument main menu and select the "Diagnostics/Simulation" option.
  2. In the submenu, select "Simulated Current Output".
  3. Enter the target current value (such as 4 mA, 12 mA, 20 mA). After confirmation, the instrument will output the corresponding current.
  4. Use a multimeter to measure at the current output terminal and verify the actual output value.
  5. After the test is completed, exit simulation mode, and the instrument will resume normal measurement output.

Note: In simulation mode, the instrument outputs a fixed current and will not change with the level. Be sure to exit after testing to avoid affecting normal production.

Prosonic 93 simulated current output wiring diagram

Simulated Current Output Parameters and Precautions

The table below lists the key parameters of the simulated current output for reference by engineering and technical personnel.

ParameterDescription
Output range4-20 mA (any value can be simulated)
Accuracy±0.1 mA (typical value)
Load resistanceMaximum 500 Ω
Simulation modeFixed current output, does not change with level

When using the simulation function, pay attention to the following points:

  • Ensure the supply voltage is within the specified range of the instrument to avoid abnormal output.
  • The simulated current output is only for commissioning and must not remain in simulation mode for a long time.
  • If the output current deviation is too large, check the wiring and load resistance.

Mastering the setup method of the Prosonic 93 simulated current output can effectively improve instrument commissioning and troubleshooting efficiency, and is an essential skill for industrial on-site maintenance personnel.