Prowirl 72 Simulated Current Output Overview

Prowirl 72 is a vortex flowmeter launched by Endress+Hauser, widely used for flow measurement of steam, gases, and liquids. Its simulated current output function allows the instrument to manually output a set 4-20mA current signal without relying on actual flow.

This function is mainly used for loop calibration, host computer signal testing, and troubleshooting, and is a practical tool for on-site commissioning and maintenance.

Prowirl 72 simulated current output

Main Uses of Simulated Current Output

On engineering sites, simulated current output can replace the real flow signal and help technicians independently verify the signal chain.

  • Loop calibration: Verify whether the 4-20mA loop from the transmitter to the PLC/DCS is accurate.
  • Troubleshooting: Distinguish whether the problem is with the instrument measurement or the downstream receiving end.
  • System integration testing: Test host computer display and alarm logic when there is no actual flow.
  • Regular maintenance: Confirm whether the current output accuracy meets process requirements.

Operation Steps

Entering Simulation Mode

  1. Ensure that the instrument is in measurement mode and is powered on.
  2. Enter the function menu through the local display or configuration software.
  3. Select the "Simulation" option.
  4. Enter the target current value (such as 4mA, 12mA, 20mA).

Exiting Simulation Mode

  1. After completing calibration, return to the simulation menu.
  2. Select "Exit Simulation".
  3. Confirm that the instrument returns to the actual flow output state.

Common Output Values and Corresponding Flow

The table below lists the correspondence between standard 4-20mA output and flow percentage for quick judgment.

Output CurrentFlow PercentageTypical Use
4 mA0%Zero point calibration
8 mA25%Low flow test
12 mA50%Midpoint calibration
16 mA75%High flow test
20 mA100%Full scale calibration

Prowirl 72 simulated current output wiring

Precautions

  • During simulation, the instrument will not respond to actual flow, so process safety must be confirmed.
  • Some versions require entering an authorization password to enter simulation mode.
  • After calibration is completed, be sure to exit simulation to avoid affecting normal measurement.
  • If the output deviation is large, it is recommended to check the loop load and wiring.

Summary

Prowirl 72 simulated current output is an efficient tool for on-site commissioning and maintenance and can quickly verify the 4-20mA loop. Mastering its operation steps and precautions helps improve the reliability and maintenance efficiency of the instrument system.