Overview of Prowirl 72 Simulation Pulse Output

Prowirl 72 is a vortex flowmeter launched by Endress+Hauser, widely used for flow measurement of steam, gases, and liquids. Its simulation pulse output function allows simulating pulse signal output without actual flow, for system integration testing and verification.

This function is of great value in engineering commissioning, PLC/DCS channel testing, and metering system acceptance. Through the simulation pulse output, it is possible to quickly confirm on site whether the signal chain is normal.

Prowirl 72 simulation pulse output schematic

Working Principle of Simulation Pulse Output

Basic Mechanism of Pulse Output

The pulse output of Prowirl 72 is usually proportional to volumetric flow or mass flow. Each pulse represents a certain accumulated flow, and the pulse equivalent can be set in the parameters.

In simulation mode, the instrument internally generates a fixed-frequency pulse signal to replace the real flow signal, thereby simulating the output behavior.

Differences Between Simulation Mode and Real Mode

Comparison ItemReal Pulse OutputSimulation Pulse Output
Signal SourceActual flow sensorInternal signal generator
PurposeNormal meteringCommissioning and verification
Output FrequencyVaries with flowFixed or configurable
Impact on SystemParticipates in meteringUsed only for testing

Configuration Steps for Simulation Pulse Output

Preliminary Preparation

  • Confirm that the Prowirl 72 is properly powered and in operating state
  • Prepare a HART handheld communicator or commissioning software (such as FieldCare)
  • Confirm that the pulse output terminals are correctly wired to the test equipment

Parameter Setting Procedure

  1. Enter the instrument menu and select the Output Settings option
  2. Find the Simulation submenu
  3. Select the Pulse Output Simulation mode
  4. Set the simulation frequency or pulse equivalent
  5. Save the parameters and exit the menu

Prowirl 72 simulation pulse output parameter setting interface

Verification and Precautions

Verification Methods

  • Use an oscilloscope or frequency counter to measure the pulse output terminals
  • Confirm that the pulse frequency matches the set value
  • Check whether the counting on the PLC/DCS side is normal

Key Precautions

  • Simulation mode is only for commissioning, and must be turned off after commissioning is completed to avoid affecting normal metering
  • During simulation, the instrument does not reflect actual flow, and it must not be used for trade settlement
  • It is recommended to record the original parameters before simulation for easy restoration
  • If there is no pulse output, check whether the wiring polarity and load resistance match

Common Problems and Solutions

SymptomPossible CauseRecommended Action
No pulse outputSimulation not activated or wiring errorCheck simulation status and terminal wiring
Large frequency deviationIncorrect pulse equivalent settingRecheck the parameters
Unstable signalElectromagnetic interference or load mismatchCheck shielding and load resistance

Summary

The simulation pulse output of Prowirl 72 is an important tool for commissioning and verification. Proper use can significantly improve the efficiency of system integration testing. Engineering personnel should strictly follow the operating procedures and ensure that the normal measurement mode is restored promptly after commissioning.